Chapter 2:-SCADA Configuration

Case Study 1:Siemens SCADA Confugration


Software used:-TIA Portal V13

Application:-RT Advanced

PLC:-S7-1200

SCADA Configuration


//////////////////////////////////////////////////////////////////////////////////////////////////////////////////////////////////////////////////////////////////////////////////////////////////////////////

Case Study 2:Push button,Switches,Graphics Configuration In RT Advanced 

1. Open →TIA portal v13
2. Create a new project
3. Give project name, path, author, comment and click on create
4. Go to →project view
5. In project tree go to →"add new device"
6. Go to → PC system>Simatic HMI application>WinCC RT advanced
7. Click → ok.
8. Go to →
Hardware catalog>pc system>communication modules>Profinet/Ethernet>IE general.
Drag and drop to Simatic PC station in device view
9. Go to → project tree>hmi_rt_1 >screen>add new screen
10. Take three buttons from tool box> elements, and also take one circle from >toolbox > basic objects
11. Rename buttons to "Start", "Stop”, and "Stop run time" and add text field below circle and give name to "Motor"
12. Go to → project tree>HMI tag>default tag table
13. Click on "add new" and add 'start tag", "stop tag", and "lamp" and data type "bool"
14. Now go to screen>screen_1>select "start button and click below its "properties"
15. In properties go to "events tab" >select "click" > double click on 'add function' and search for "set bit", after selection in place of "tag(input/output" assign "start tag".
16. Now select "stop button" properties >event>click> search for "invert bit"> assign "start" tag
17. Click lamp > properties> animation>appearance >dynamic colors and flashing
18. Add tag name" Start" in below table add range "0" and "1" set back ground color "red for "0", and "green for "1".
19. Now select "Run time Stop” button properties >event>click> search for "stop runtime"
20. Compile the project.
21. Start "runtime"