Motor jog control is an industrial motor control technique that allows a motor to run for a short duration while a jog push button is pressed. When the button is released, the motor stops. It is commonly used for precise positioning, machine setup, conveyor alignment, and maintenance operations.

Functional schematic overview for the PLC
application.
I/O and Internal Tags
|
Area |
Tag |
Type |
Default |
Description |
|
INPUT |
StartPB |
Bool |
|
|
|
INPUT |
StopPB |
Bool |
|
|
|
INPUT |
ResetPB |
Bool |
|
|
|
INPUT |
AutoMode |
Bool |
TRUE |
|
|
INPUT |
EStopOK |
Bool |
|
|
|
INPUT |
Permissive1 |
Bool |
|
|
|
INPUT |
Permissive2 |
Bool |
|
|
|
INPUT |
FeedbackOK |
Bool |
|
|
|
INPUT |
FeedbackDelay |
Time |
T#3s |
|
|
OUTPUT |
RunCommand |
Bool |
|
|
|
OUTPUT |
RunLamp |
Bool |
|
|
|
OUTPUT |
ReadyLamp |
Bool |
|
|
|
OUTPUT |
FaultLamp |
Bool |
|
|
|
OUTPUT |
FaultCode |
Int; |
|
0 none, 1
estop, 2 permissive1, 3 permissive2, 4 feedback |
|
VAR |
StartPB |
Bool |
|
|
|
VAR |
StopPB |
Bool |
|
|
|
VAR |
ResetPB |
Bool |
|
|
|
VAR |
AutoMode |
Bool |
TRUE |
|
|
VAR |
EStopOK |
Bool |
|
|
|
VAR |
Permissive1 |
Bool |
|
|
|
VAR |
Permissive2 |
Bool |
|
|
|
VAR |
FeedbackOK |
Bool |
|
|
|
VAR |
FeedbackDelay |
Time |
T#3s |
|
SCL Program
// Application 002: Motor Jog Control
// Category: Motor and Drive Control
// PLC: Siemens S7-1200
// Language: SCL for TIA Portal
// Note: Training template. Validate all safety and
machine behavior before commissioning.
FUNCTION_BLOCK "FB_002_MotorJogControl"
{ S7_Optimized_Access := 'TRUE' }
VERSION : 1.0
VAR_INPUT
StartPB : Bool;
StopPB : Bool;
ResetPB : Bool;
AutoMode : Bool
:= TRUE;
EStopOK : Bool;
Permissive1 :
Bool;
Permissive2 :
Bool;
FeedbackOK :
Bool;
FeedbackDelay :
Time := T#3s;
END_VAR
VAR_OUTPUT
RunCommand :
Bool;
RunLamp : Bool;
ReadyLamp :
Bool;
FaultLamp :
Bool;
FaultCode :
Int; // 0 none, 1 estop, 2 permissive1, 3 permissive2, 4 feedback
END_VAR
VAR
RunLatch :
Bool;
FeedbackTimer :
TON;
FeedbackFault :
Bool;
END_VAR
BEGIN
IF ResetPB AND
EStopOK AND Permissive1 AND Permissive2 THEN
FeedbackFault := FALSE;
FaultCode
:= 0;
END_IF;
IF NOT EStopOK
THEN
FaultCode
:= 1;
ELSIF NOT
Permissive1 THEN
FaultCode
:= 2;
ELSIF NOT
Permissive2 THEN
FaultCode
:= 3;
ELSIF
FeedbackFault THEN
FaultCode
:= 4;
END_IF;
IF StopPB OR
(FaultCode <> 0) OR NOT AutoMode THEN
RunLatch :=
FALSE;
ELSIF StartPB
AND AutoMode AND EStopOK AND Permissive1 AND Permissive2 AND (FaultCode = 0)
THEN
RunLatch :=
TRUE;
END_IF;
RunCommand :=
RunLatch AND AutoMode AND EStopOK AND Permissive1 AND Permissive2 AND
(FaultCode = 0);
FeedbackTimer(IN := RunCommand AND NOT FeedbackOK, PT := FeedbackDelay);
IF
FeedbackTimer.Q THEN
FeedbackFault := TRUE;
RunLatch :=
FALSE;
FaultCode
:= 4;
END_IF;
RunLamp :=
RunCommand AND FeedbackOK;
ReadyLamp :=
AutoMode AND EStopOK AND Permissive1 AND Permissive2 AND (FaultCode = 0) AND
NOT RunCommand;
FaultLamp :=
FaultCode <> 0;
END_FUNCTION_BLOCK
Commissioning reminder: validate all I/O mapping,
permissive behavior, feedback wiring, emergency-stop circuits, and local safety
requirements before running real equipment.
Commissioning Checklist
·
Map every PLC tag to the correct
physical input, output, HMI tag, or memory address.
·
Compile in TIA Portal and adjust
tag names, timers, and setpoints for the real machine.
·
Test normal sequence, stop, reset,
feedback failure, timeout, and alarm conditions in simulation first.
·
Use certified safety hardware or
fail-safe logic for emergency stops, guards, and hazardous motion.
No comments: